Keypoints
- Autonomous packaged unit for heat production which does not require thermal station or hot water supply.
- Maximum energy efficiency with condensing operation at reduced heating capacity and yield greater than 100%.
- Heat exchanger completely made of stainless steel resistant to corrosion.
- Can be combined with gas or diesel blown burners, with two-stage or modulating regulation.
- Wide range consisting of 9 models with heating capacity up to 1.160 kW.
- Special conveyors on the air intake.
- Complete of safety devices (thermostats FAN/LIMIT and flow switch).
- Possibility of installation in circuits with positive and negative pressure.
Warm Air Heaters
SR-ENERGY Condensing air heating sections for inside installation
Oil
to 71.000
The condensing air heating sections for inside installation SR-ENERGY is a module to be installed in a preexisting and/or dedicated aeraulic system. It has been designed for air heating purposes.
This equipment is to be employed in the framework of traditional air treatment for civil and/or commercial use, whenever specific performances are required.
Product informations
Description |
U.M. |
SR-ENERGY |
SR-ENERGY 105 |
SR-ENERGY 160 |
SR-ENERGY 220 |
---|---|---|---|---|---|
Max nominal heating capacity input (burned) |
kW |
68,2 |
115,1 |
175,7 |
246,1 |
kcal/h |
58.650 |
98.986 |
151.105 |
211.650 |
|
Max USEFUL heating capacity output |
kW |
60,1 |
103,5 |
160,3 |
217,1 |
kcal/h |
51.686 |
89.010 |
137.858 |
186.706 |
|
Min USEFUL heating capacity output |
kW |
22,7 |
37,1 |
55,9 |
66,5 |
kcal/h |
19.540 |
31.950 |
48.040 |
57.155 |
|
Min/Max airflow |
Nm3/h |
4.600/7.000 |
8.000/12.000 |
11.000/17.000 |
15.000/23.000 |
Description |
U.M. |
SR-ENERGY 320 |
SR-ENERGY 460 |
SR-ENERGY 640 |
SR-ENERGY 970 |
---|---|---|---|---|---|
Max nominal heating capacity input (burned) |
kW |
349,8 |
502,9 |
715,2 |
1.089,8 |
kcal/h |
300.830 |
432.495 |
615.045 |
937.230 |
|
Max USEFUL heating capacity output |
kW |
323,9 |
465,2 |
648,6 |
970,0 |
kcal/h |
278.554 |
400.072 |
557.796 |
834.200 |
|
Min USEFUL heating capacity output |
kW |
119,9 |
196,8 |
159,7 |
234,3 |
kcal/h |
103.115 |
169.265 |
137.370 |
201.150 |
|
Min/Max airflow |
Nm3/h |
21.500/33.000 |
31.000/47.000 |
43.000/65.000 |
71.000/110.000 |
Model |
Dimensions mm |
Chimney Ø mm |
Weight kg |
Weight (with package) kg |
||
---|---|---|---|---|---|---|
A |
B |
C |
||||
SR-ENERGY 60 |
1.400 |
830 |
685 |
150 |
200 |
210 |
SR-ENERGY 105 |
1.540 |
1.060 |
900 |
200 |
225 |
235 |
SR-ENERGY 160 |
1.630 |
1.300 |
1.040 |
250 |
350 |
361 |
SR-ENERGY 220 |
1.740 |
1.500 |
1.145 |
250 |
430 |
442 |
SR-ENERGY 320 |
1.860 |
1.700 |
1.350 |
300 |
560 |
576 |
SR-ENERGY 460 |
2.210 |
2.090 |
1.430 |
300 |
810 |
828 |
SR-ENERGY 640 |
2.460 |
2.500 |
1.670 |
350 |
1.080 |
1.104 |
SR-ENERGY 970 |
2.460 |
3.500 |
1.680 |
400 |
1.550 |
1.555 |
AIR HEATING SECTION consisting of:
- Heat exchanger three smokes rounds, with combustion chamber made of AISI 430 stainless steel, smoke pipes in AISI 304 stainless steel including turbolators, exhaust manifold with condensate discharge, inspection doors, chimney connection and burner mounting plate with insulation.
- External casing in pre-painted or powder-coated galvanized steel with insulation, support frame and duct connection flanges.
- Special conveyors on the air inlet section to achieve the best cooling of the heat exchanger.
- Electrical protection equipment consisting of a FAN-LIMIT double-thermostat (n. 1 for manual reset and n. 1 for automatic reset).
- Support frame in galvanized steel inclined towards the condensate drain.
PACKAGE: Air heating sections are wrapped in plastic film.