Warm Air Heaters
CMX Condensing suspended gas-fired room sealed heaters
for duct systems with premix modulating gas burnerto 13.000
CMX - air treatment units for indoor or outdoor installation (using a special kit). Premix condensing units with centrifugal fan and the possibility of treating and mixing both outdoor air and air returning from the environment.
Product informations
Condensing sealed warm air heaters with modulating premix gas burner, CMX range, are designed to be installed inside the building or outside (with a special kit) and allowing diffusion of the air by ducted systems. The CMX heaters are equipped with centrifugal fans with energy efficient motors to ensure the air pressure necessary for distribution through air ducts and diffusers. The unit operates with variable thermal power with continuous modulation, fully automatically regulated from the remote control panel with integrated or remote environment temperature probe. The warm air heaters, thanks to the continuous modulation of the thermal capacity, decreases automatically the heating power, reaching performance values of up to 106%, consuming less fuel and ensuring ideal comfort and significant overall operating economy.
The CMX warm air heaters finds application in the heating of industrial and commercial environments, facilities for sports, entertainment, etc.
Tecnoclima premix gas suspended warm air heaters have many advantages:
- heat capacity of the premix burner has a wide modulation range: from 100 % to 30 % of the nominal heat capacity;
- thanks to the modulation of the thermal capacity, as the demand for heat from the environment decreases, very high e ciency values are reached, up to 106%, with many benefi ts in terms of environmental comfort and the reduction of gas consumption;
- the premix burner allows perfect mixing of the gas with the combustion air obtaining a semi-radiant fl ame band with very low emissions of nitrogen oxides, NOx: Class 5 of emissions;
- very high thermal effi ciency and progressive modulation of the thermal power contribute to obtain operating cost savings of over 30 % compared to traditional systems.
Description |
U.M. |
CMX 30 |
CMX 40 |
CMX 50 |
---|---|---|---|---|
Max nominal heating capacity input (burned) |
kW |
29,1 |
38,5 |
49,8 |
kcal/h |
25.057 |
33.111 |
42.822 |
|
Max USEFUL heating capacity output |
kW |
28,0 |
37,0 |
48,0 |
kcal/h |
24.080 |
31.820 |
41.280 |
|
Min USEFUL heating capacity output |
kW |
10,0 |
14,0 |
19,0 |
kcal/h |
8.600 |
12.040 |
16.340 |
|
Nominal air flow |
Nm3/h |
3.200 |
4.400 |
5.500 |
Useful static pressure |
Pa |
200/450 |
200/450 |
200/450 |
Description |
U.M. |
CMX 60 |
CMX 90 |
CMX 120 |
---|---|---|---|---|
Max nominal heating capacity input (burned) |
kW |
59,0 |
90,8 |
116,0 |
kcal/h |
50.745 |
78.102 |
99.760 |
|
Max USEFUL heating capacity output |
kW |
57,0 |
89,0 |
115,0 |
kcal/h |
49.020 |
76.540 |
98.900 |
|
Min USEFUL heating capacity output |
kW |
21,0 |
35,0 |
43,0 |
kcal/h |
18.060 |
30.100 |
36.980 |
|
Nominal air flow |
Nm3/h |
6.500 |
10.000 |
13.000 |
Useful static pressure |
Pa |
200/450 |
200/450 |
NOTES200/450 |
NOTES:
The warm air heaters CMX are designed for indoor installation. Kit for outdoor installation available as accessory.
The warm air heaters CMX are set to G20 natural gas. The conversion kit to natural gas G25 (where applicable) or propane gas G31 can be ordered separately (see accessories).
The remote control panel is a mandatory accessory for correct operation of the heaters.
Model |
Dimensions mm |
Chimney Ø mm |
Air connection Ø mm |
Weight kg |
Weight (with package) kg |
|||
---|---|---|---|---|---|---|---|---|
A |
B |
C |
||||||
CMX |
30 |
979 |
1300 |
778 |
80 |
80 |
117 |
139 |
CMX |
40 |
979 |
1300 |
778 |
80 |
80 |
120 |
145 |
CMX |
50 |
1319 |
1450 |
848 |
80 |
80 |
162 |
192 |
CMX |
60 |
1319 |
1450 |
848 |
80 |
80 |
170 |
205 |
CMX |
90 |
1869 |
1650 |
998 |
100 |
100 |
295 |
337 |
CMX |
120 |
1869 |
1650 |
998 |
100 |
100 |
312 |
357 |
CONDENSING WARM AIR HEATER consisting of:
- Heat exchanger with combustion chamber made of AISI 430 stainless steel, with smoke pipes made of AISI 304 stainless steel with turbulence imprints, complete with inspection door, chimney connection and condensate discharge connection
- External casing made of pre-painted or powder-coated galvanized steel, with thermal insulation.
- Premix modulating burner with low CO and NOx emissions (Class 5), with wide regulation range, including semi-radiant flame tubular, modulating mixer and gas-air solenoid valve, DC brushless fan, ignition and ionisation electrodes for flame control.
- Centrifugal fan complete with electrical motor and variable belt transmission. 400V 50Hz 3N power supply.
- Air inlet plenum containing the fan group, complete with safety grid and designed for the possible connection of an air intake duct.
- Multifunctional electronic board for control and protection of the warm air heater: ambient temperature control, burner start up, flame supervision and safety functions.
- Multifunctional LED indicator to signal operating conditions or the presence of the main anomalies.
- Safety temperature probe for overheating shutdown.
- Air outlet flange for connection of the air outlet duct.
- Combustion air intake connection.
- Flue exhaust connector complete with a sampling well for combustion products.
- Siphon for the condensate discharge.
PACKAGE: Warm air heaters are packed in cardboard and pallet-loaded.