Keypoints
- Ideal in case of limited height of the room as well as for raised or suspended installation to avoid obstructions on the floor
- Maximum energy efficiency and environmental comfort thanks to power modulation and condensation operation at reduced thermal load
- Heat exchanger made entirely of stainless steel AISI 304 with aerodynamic profile and turbulent imprints
- High efficiency ~ 103%
- Can be combined with gas or diesel blown air burners, with two-stage or modulating operation
- 8 models with thermal capacity from 20 kW to 1.100 kW and air flow from 4.600 to 71.000 m3/h
- Suitable for ducted or direct diffusion systems with air outlet plenum
Warm Air Heaters
ENERGY-O Condensing horizontal warm air heaters for inside installation
Oil
to 71.000
Tecnoclima cabinet warm air heaters ENERGY-O are the ideal solution for heating and controlled ventilation of medium large areas such as workshops, laboratories, industrial halls, warehouses, gyms, shopping centers, exhibition halls, theaters, churches, etc.
Product informations
External casing in pre-painted or powder-coated galvanized steel with insulation.
Heat exchanger three smokes rounds, with combustion chamber made of AISI 430 stainless steel, smoke pipes in AISI 304 stainless steel including turbolators, exhaust manifold with condensate discharge, inspection doors, chimney connection and burner mounting plate with insulation.
Fan section with one or more high performance centrifugal fans, complete with electric motor and variable belt transmission.
Electrical board for control and protection of the warm air heater designed for three phase electrical motor supply 400V 50Hz 3N, complete with FAN-LIMIT double thermostat (n°1 with manual reset and n°1 with automatic reset).
Description |
U.M. |
ENERGY 60 O |
ENERGY 105 O |
ENERGY 160 O |
ENERGY 220 O |
---|---|---|---|---|---|
Max nominal heating capacity input (burned) |
kW |
68,2 |
115,1 |
175,7 |
246,1 |
kcal/h |
58.650 |
98.986 |
151.105 |
211.650 |
|
Max USEFUL heating capacity output |
kW |
60,1 |
103,5 |
160,3 |
217,1 |
kcal/h |
51.686 |
89.010 |
137.858 |
186.706 |
|
Nominal air flow |
Nm3/h |
4.600 |
8.000 |
11.000 |
15.000 |
Useful static pressure |
Pa |
220 |
220 |
220 |
220 |
Description |
U.M. |
ENERGY 320 O |
ENERGY 460 O |
ENERGY 640 O |
ENERGY 970 O |
---|---|---|---|---|---|
Max nominal heating capacity input (burned) |
kW |
349,8 |
502,9 |
715,2 |
1.089,8 |
kcal/h |
300.830 |
432.495 |
615.045 |
937.230 |
|
Max USEFUL heating capacity output |
kW |
323,9 |
465,2 |
648,6 |
970,0 |
kcal/h |
278.554 |
400.072 |
557.796 |
834.200 |
|
Nominal air flow |
Nm3/h |
21.500 |
31.000 |
43.000 |
71.000 |
Useful static pressure |
Pa |
220 |
220 |
220 |
220 |
Model |
Dimensions mm |
Chimney Ø mm |
Weight kg |
Weight (with package) kg |
||||
---|---|---|---|---|---|---|---|---|
A |
A1 |
B |
C |
E |
||||
ENERGY 60 O |
1.580 |
– |
870 |
675 |
- |
150 |
180 |
200 |
ENERGY 105 O |
1.926 |
– |
1.060 |
900 |
- |
200 |
320 |
340 |
ENERGY 160 O |
2.120 |
– |
1.300 |
1.045 |
100 |
250 |
480 |
505 |
ENERGY 220 O |
2.550 |
– |
1.500 |
1.145 |
100 |
250 |
600 |
625 |
ENERGY 320 O |
2.750 |
– |
1.700 |
1.350 |
100 |
300 |
800 |
830 |
ENERGY 460 O |
1.400 |
1.870 |
2.090 |
1.430 |
100 |
300 |
1.250 |
1.285 |
ENERGY 640 O |
1.400 |
2.120 |
2.500 |
1.670 |
100 |
350 |
1.800 |
1.840 |
ENERGY 970 O |
1.600 |
2.120 |
3.500 |
1.680 |
100 |
400 |
2.200 |
2.245 |
CONDENSING WARM AIR HEATER consisting of:
- Heat exchanger three smokes rounds, with combustion chamber made of AISI 430 stainless steel, smoke pipes in AISI 304 stainless steel including turbolators, exhaust manifold with condensate discharge, inspection doors, chimney connection and burner mounting plate with insulation.
- External casing in pre-painted or powder-coated galvanized steel with insulation.
- Support frame in galvanized steel, inclined toward the condesate drain.
- Fan section with one or more high performance centrifugal fans, complete with electric motor and variable belt transmission.
- Electrical board for control and protection of the warm air heater designed for three phase electrical motor supply 400V 50Hz 3N, complete with FAN-LIMIT double thermostat (n° 1 with manual reset and n° 1 with automatic reset).
- Air inlet section open on two sides (upper and side). Closing panels have to be selected from the list of accessories by the customer depending on the air inlet position.
PACKAGE: Warm air heaters are wrapped in plastic film.
-
Top panel
-
Side panel
-
Safety top grid for air intake
-
Safety side grid for air intake
-
Top air inlet filter
-
Side air inlet filter